Gf-signet 5090 Sensor-Powered ProPoint Flow Monitor Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Werkzeug Gf-signet 5090 Sensor-Powered ProPoint Flow Monitor herunter. GF Signet 5090 Sensor-Powered ProPoint Flow Monitor User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 4
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
Sensor Frequency = ___________________________ Hz
Technical note:
Sensor frequency MUST be greater than 45 Hz for full scale
needle de ection.
3. Calculate the actual max. ow rate in your process line as follows:
Maximum ow rate = Sensor frequency (step 2) × A-Factor (Section 6)
Maximum Flow Rate = __________________________________
2. Calibration
The 5090/515 ow metering system utilizes the AC signal
amplitude from the 515 sensor to drive the 5090 meter.
The front panel meter movement adjustment (SPAN) is easily
accessed under the removable front window for simple calibration.
A dial kit with six dial ranges, assorted ow unit/multiplier decals,
and dial installation instructions is included for your convenience.
1. Compatible Sensor Wiring
Frequency
counter
Red
Black
10
0
1
2
3
4
5
6
7
8
9
GPM
X100
SPAN
Signet Monitor
4. Install the appropriate dial face and ow unit/multiplier decal
for the maximum ow rate (Step 3). Refer to dial installation
instructions included with dial kit.
The dial kit includes the following:
Example: A ow system's maximum ow rate is 18.3 GPM.
The proper dial and ow unit/multiplier decal for this ow system is:
0 - 2 dial + GPM × 10 decal.
5. Disconnect frequency counter.
Access and adjust the "SPAN" potentiometer to match the
calculated maximum ow rate from Step 3.
After adjustment, calibration is complete.
5090
Rotor
w/magnets
Black
Red
515 Circuit
Shield
SPAN
0
1
2
3
8
6
7
5
4
9
X 100
GPM
10
SPAN
Signet Monitor
6 Dials:
0-2
0-4
0-6
0-8
0-10
0-100
Assorted Unit and Multiplier Decals:
X 10
X 100
X 1,000
X 10,000
LPM
x 1,000
GPM
x 10
m
3
/h
SPAN
0
1
2
3
8
6
7
5
4
9
10
SPAN
0
1
2
SPAN
0
1
2
SPAN
0
1
2
3
8
6
7
5
4
9
10
Signet 5090 Flow Monitor
Technical Notes:
Remove terminal block for easy wiring (Fig. 1)
Maintain cable shield through cable splice.
Route sensor cable away from AC power lines.
Use 2-conductor shielded cable for sensor cable extension up
to 61 m (200 ft).
English
Red
Blk
Shld
Sensor
Input
515
Black (AC signal out)
Red (AC signal out)
Silver (shield)
5090 Rear
Terminal
Connection
Red
Blk
Shld
Sensor
Input
Red
Blk
Shld
Sensor
Input
LISTED
77CJ
U
L
Fig. 1
*3-5090.090-1*
3-5090.090-1 Rev. K 08/13
Procedure
1. Induce the maximum (stable) ow rate in your process line.
2. Using the frequency counter, monitor and record the 515
sensor frequency output:
Equipment Required
• Frequency counter
Signet 515 Sensor installed in process line
Standard and phillips head screwdriver
Seitenansicht 0
1 2 3 4

Inhaltsverzeichnis

Seite 1 - Signet 5090 Flow Monitor

Sensor Frequency = ___________________________ HzTechnical note: Sensor frequency MUST be greater than 45 Hz for full scale needle defl ection.3. Calcu

Seite 2 - 5. Maintenance

2Signet 5075 Flow MonitorSIDE VIEW Mounting Clamp (2 ea.) Optional Splashproof Rear Cover 88 mm (3.5 in.) Mounting Panel Panel Gasket 91 mm (3.6 in.)

Seite 3

3Signet 5090 Flow Monitor 6. Signet 515 Flow Sensor A-Factors-------------- A-FACTORS ----------------PIPESIZESIGNETFITTING------------------- 1 Hz =

Seite 4 - A-Factors for DIN Pipes

------------------------------ A-FACTORS -------------------------------PIPESIZESIGNETFITTING---------------------------------- 1 Hz = ---------------

Kommentare zu diesen Handbüchern

Keine Kommentare